The 1960 series is designed to meet or exceed the requirements of MIL-STD-220 with 100dB attenuation from 14 kHz to 1 GHz. These filters are capable of carrying full rated current without exceeding a 25°C temperature rise above ambient temperature. LCR 1960 series filters can be operated continuously at their rated currents and voltages and are capable of withstanding a 40% current overload for 15 minutes without degradation. (Suffix "N" in the Part Number Table below indicates grounded terminals for Neutral Line connection.)
Power line filters are designed to protect and facilitate secure communications for shielded rooms and buildings. Individual filters are installed in a weld steel cabinet protected by electro-tin plating to withstand corrosion and extreme environmental (temperature, moisture and so on) conditions.